7
vacon • 64
Commissioning
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
7.4
Quick instructions for controlling the motor
This chapter gives quick instructions on how to get the motor running using either CiA-402 velocity
or Bypass mode using SDO protocol.
1.
Set the OPTE6 jumpers, refer to Chapter 5.3
2.
Install OPTE6 option board in VACON® AC drive and connect the CAN cable, refer to chapter 6
and 5.1
3.
Set the option board parameters to establish CANopen communication. Refer to chapter 7.1.
4.
Set the AC drive parameters so that it is controlled over fieldbus. Refer to Chapter 11 Appendix
B - Fieldbus parametrization
Drive profile:
Motor control mode should be set to Speed control. If it is not, Statusword has bit 0x4000 set.
If Statusword bit 0x200 is not set, the AC drive is not in fieldbus control mode and cannot be started
via CANopen.
5.
Set Controlword (0x6040) to 0x00
•
Statusword (0x6041) is 0x270
6.
Set Controlword to 0x06
•
Statusword is 0x4231
7.
Set Controlword to 0x0F
•
AC drive starts, Statusword is 0x637
8.
Set vl target velocity (0x6042) to 500 (rpm)
•
Motor starts to run at 500 rpm (0x6044 vl velocity actual value)
•
If actual velocity does not change, check that AC drive reference is set to fieldbus
Bypass:
Motor control mode must be set to Frequency (if reference is given as percentage of maximum fre-
quency).
5.
Set FB Control Word (0x2000:01) to 0x00
•
FB Status Word (0x2001:01) is 0x41
6.
Set FB Control Word to 0x01
•
AC drive starts, FB Status Word is 0x23
•
If AC drive does not start, check that AC drive is in fieldbus control mode
7.
Set FB Speed Reference (0x2000:03) to 2500 = 25.00% of maximum frequency. Usually default
value for maximum frequency is 50.00 Hz, so in this case the reference is 12.50 Hz.
•
FB Actual Speed (0x2001:03) is 2500 = 25.00% output frequency of maximum frequency
•
If actual speed does not change, check that AC drive reference is set to fieldbus
If motor control mode is set to Speed, the reference is given as a percentage of maximum frequency
converted to rpm. In this case the FB Actual Speed should not be read as this holds the percentage
related to output frequency. Therefore, the actual speed should be from process data out 2 (by de-
fault set to speed in rpm).