CANopen protocol description
vacon • 21
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
3
3.7
Communication objects
3.7.1
0X1000 - Device Type
The device type object indicates basic information about the device, including the supported device
profile and the profile settings.
Value description:
0x0192 = 402 (Drive profile)
0x0001 = AC drive with PDO set for a generic drive device
3.7.2
0X1001 - Error Register
Error register indicates the active error code.
* Not used/supported
Table 32: 0x1000 Device type
Index
Sub-index
Value
Name
Data type
Access
0x1000
-
0x00010192
Device type
UNSIGNED32
const
Table 33: 0x1001 Error register
Index
Sub-index
Value
Name
Data type
Access
0x1001
-
0x0
Error register
UNSIGNED8
ro
Table 34: Error register bit descriptions
Bit
Meaning
0
Generic error
1
Current
2
Voltage
3
Temperature
4
Communication error (overrun, error state)
5
Device profile-specific*
6
Reserved*
7
Manufacturer-specific*