Appendix B - Fieldbus parametrization
vacon • 99
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
11
11.2
Response to fieldbus fault
In case of a fieldbus fault (loss of connection etc.), a fieldbus fault is triggered. This fault can be
parameterized in application to result in a desired response. Always check the application specific
manual for details as responses vary between used applications. For common fault responses used
commonly in standard applications, see the table below.
Modbus TCP/
UDP
7
Only process data from VACON
®
100 family internal Modbus
TCP/UDP protocol is forwarded to application
Bacnet IP
8
Only process data from VACON
®
100 family internal Bacnet
IP protocol is forwarded to application
Table 125. Response to fieldbus fault in VACON
®
AC drives
ID
AC Drive
Value
Default
Panel Tree
733
VACON
®
100
family
0 = No action
1 = Alarm
2 = Alarm + preset frequency
3 = Fault: Stop function
4 = Fault: Coast
3
P3.9.1.6
VACON
®
20
P13.19
VACON
®
20 X
0 = No action
1 = Warning
2 = Fault
2
P9.15
VACON
®
NXP
0 = No action
1 = Warning
2 = Fault: Stop function
3 = Fault: Coast
2
P2.7.22
Table 124.
Value name
Value
Description