8
vacon • 82
CANopen option board interface
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
8.4.6
FB Status Word
Mapped into FB PD out offset 0.
Table 106. FB Status Word
Table 107. FB Status word description
8.4.7
FB Status Word Extension (general status word)
Mapped into FB PD out offset 1.
Table 108. FB Status word extension
8.4.8
FB Actual Speed
Mapped into FB PD out offset 2.
Table 110. FB Actual Speed
Table 111. FB Actual Speed description
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
-
-
-
-
-
-
-
-
FRDY ZSPD ATREF ALARM
FLT
DIR
RUN
RDY
Bit
Name
Description
0
1
7
FRDY
Flux ready
Motor magnetization is ready
-
Flux ready
6
ZSPD
Zero speed
Motor is running on zero speed
-
Zero speed condition
5
ATREF
At reference
Reference frequency is reached
-
Reference reached
4
ALARM
Alarm
Alarm indication
-
Drive is in Alarm
3
FLT
Faulted
Drive fault indicatioin
-
Drive is Faulted
2
DIR
Direction
Motor running direction
Clockwise
Counter clockwise
1
RUN
Run
Motor running information
Stopped
Running
0
RDY
Ready
Drive readiness information
-
Ready
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
CP3
CP2
CP1
-
-
-
-
-
-
-
-
-
-
-
-
-
Table 109. FB Status word extension description
Bit
Name
Description
0
1
15
CP3
Control Place
Drive Control place information
0,0,1-(1) Fieldbus
0,1,0- (2) Panel
0,1,1 - (3) Tool
1,0,0 - (4) I/O
14
CP2
13
CP1
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
FB Actual Speed
Name
Description
Min
Max
FB Actual Speed
Actual output frequency at percentage
between minimum and maximum frequency.
Status word bit DIR is used to indicate actual
direction.
0
(0%)
10000
(100.00%)