Remount the AC drive cover and run the cable as
shown in picture.
NOTE:
When planning the cable runs, remember
to keep the distance between the fieldbus cable
and the motor cable at a
minimum of 30 cm
. It is
recommended to route the option board cables
away from the power cables as shown in the pic-
ture.
10
The bus termination must be set for the first and the last device of the fieldbus
line. See picture below. See also step 7 on page 38. We recommend that the first
device on the bus and, thus, terminated was the Master device.
9202.emf
Fieldbus
cables
Fieldbus cable
= Bus termination
Termination
activated
Termination
activated
with
jumper
Termination
deactivated
Vacon 100 Vacon 100 Vacon 100 Vacon 100
Vacon 100
3007.emf