CANopen protocol description
vacon • 9
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
3
3.
CAN
OPEN
PROTOCOL
DESCRIPTION
3.1
NMT
NMT network management manages CANopen, and is a mandatory, common feature for all
devices. The protocol describes several node control services and the state machine.
Figure 1. NMT state machine
1 = When the power is on, the NMT state is entered autonomously
2= The NMT state initialisation is finished, the NMT pre-operational state is entered
automatically
3 = NMT service starts with remote node indication or by local control
4 and 7 = NMT service enters pre-operational indication
5 and 8 = NMT service stops remote node indication
6 = NMT service starts remote node indication
9, 10 and 11 = NMT resets node indication
12, 13 and 14 = Indication of NMT service reset communication
Boot-up protocol
After a
node starts, it will enter automatically into the pre-operational state. Always when this
transition occurs, a boot-up message is sent into the bus.
Table 1: Boot-up message
CAN ID
LENGTH
DATA0
DATA1
DATA2
DATA3
DATA4
DATA5
DATA6
DATA7
0x700 +
Node ID
1
0
(1)
(2)
(11)
(4)
(5)
(10)
(7)
(3)
(14)
(13)
(12)
(8)
(9)
Power on or hardware reset
Pre-operational
Initialisation
Operational
Stopped