7
vacon • 58
Commissioning
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Any heartbeat consumer entry using the new Node ID is reset to default value. No other parameters
are affected.
If special PDO communication settings are used, these settings are overwritten and must be re-
stored. They can be restored from bus, panel or PC-tool. It is recommended to create a user set
(with PC-tool) before changing the Node ID setting and restoring it after changing Node ID (and Op-
erate Mode).
Changing of Operate Mode:
V008
and earlier: All CANopen communication parameters are restored to use operate mode spe-
cific default values.
V009
forwards: Only PDO communication and mapping parameters are restored to use mode spe-
cific default values. CANopen communication objects such as Heartbeat and Node guarding are not
modified.
Using "Restore from Set" parameter:
When writing any value (other than zero) to this parameter, all CANopen communication parame-
ters are restored to default parameters and PDO communication and mapping parameters are re-
stored to default parameters of the currently active operate mode.
Node ID, operate mode, baud rate, communication timeout and mode parameters are not affected.
After the restore the parameter value is set back to zero automatically.
7.1.3
Parameter restore
From VACON
®
100 (INDUSTRIAL V027 and FLOW V018) and OPTE6 V009 firmware version forwards,
storing and restoring of CANopen parameters is possible using either Keypad or VACON
®
Live PC-
tool.
If older version of OPTE6 or VACON
®
100 is used, parameter restore does not restore CANopen
communication parameters. In this case, the old parameters that were stored in OPTE6 option
board remain active. This means all parameters must be rewritten from bus if the option board is
changed or parameters are cleared.
0x1801:01
(TPDO2) COB-ID
0x280 + Node ID
0x80 Node ID
0x1802:01
(TPDO3) COB-ID
0x380 + Node ID
0x80 Node ID
Object
Name
New value if enabled New value if disabled