Commissioning
vacon • 59
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
7
7.2
OPTE6 Panel Monitor Values
Different number of panel monitoring values are visible depending on the used AC drive and ver-
sion. VACON
®
20 family option board monitoring values are under SYS menu.
From VACON
®
100 (INDUSTRIAL V027 and FLOW V018) and OPTE6 V009 firmware version forwards,
the active CANopen object values are visible as monitoring values. These values are the currently
active settings and are equal to values read via CANopen objects. These objects might have different
values than the stored parameters, depending if parameters written via bus are stored or not. The
values are divided into subfolders same way as the corresponding parameters.
Table 58. OPTE6 Monitoring Values
Panel code
Parameter
Format
Description
VACON
®
100
family
VACON
®
20
family
V5.x.2.1
V2.1
CANopen Status
NNNN.Y
NNNN = A running counter for incoming messages
Y = Node CANopen status, see Table 59
V5.x.2.2
-
Drive CW
-
Control word sent to AC drive from OPTE6
V5.x.2.3
-
Drive SW
-
Status word received from AC drive
V5.x.2.4
-
Protocol CW
-
Control word received from CANopen protocol
V5.x.2.5
-
Protocol SW
-
Status word sent to CANopen protocol
Table 59. Node CANopen status
Value
Description
0
Initialising
4
Stopped
5
Operational
6
Pre-operational
7
Reset application
8
Reset communication