Appendix B - Fieldbus parametrization
vacon • 97
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
11
11.
A
PPENDIX
B - F
IELDBUS
PARAMETRIZATION
The following chapter describes briefly how to parametrize the AC drive in order for the motor to be
controllable via fieldbus. These instructions are written for some basic applications. For more
information, see the application-specific manual.
In order for the AC drive to accept commands from the fieldbus network, the control place of the AC
drive has to be set to fieldbus. The default value of the parameter "Control Place" is usually I/O. Note
that if the control unit software is updated, the default settings are restored. In addition, some
applications may have the remote speed reference selection set by default to other than fieldbus. In
these cases, the speed reference selection must be set to fieldbus, in order for the speed reference
to be controlled via fieldbus.
NOTE!
The motor control mode should be selected to support the used process and profile.
11.1
Fieldbus control and reference selection
The following tables list some of the parameters related to fieldbus control in case of standard
applications for the VACON
®
100 family, VACON
®
NXP, VACON
®
20 and VACON
®
20X AC Drives. See
the application specific manuals for more detailed information and latest updates.
The parameters can be read and written by using the drive panel, PC Tools or fieldbus protocol. For
instructions on fieldbus writing, see the fieldbus specific manual.
Table 120. Fieldbus parameterization for VACON
®
100 family (standard application)
Parameter name
ID
Value
Default
Panel Tree
Control mode
600
0 = Frequency
1 = Speed
2 = Torque
0
P3.1.2.1
Remote control place
172
1 = Fieldbus CTRL
0
P3.2.1
Local / remote
211
0 = Remote
0
P3.2.2
Fieldbus ref. sel.
122
3 = Fieldbus
3
P3.3.1.10
Controlling fieldbus
2539
1 = Automatic
2 = Slot D
3 = Slot E
1
P5.13.1
Table 121. Fieldbus parametrization for VACON
®
20 (standard application)
Parameter name
ID
Value
Default
Panel Tree
Motor control mode
600
0 = Frequency
1 = Speed
2 = Torque
0
P1.8
Rem. Control place 1 sel.
172
1 = Fieldbus CTRL
0
P2.1
Local / remote
211
0 = Remote
0
P2.5
Rem. Control place 1 freq. ref. sel.
122
3 = Fieldbus
7
P3.3