E6581442
I-13
9
Safety category1:
EN954-1 category1, IEC/EN61508, SIL1
Stop category0:
IEC/EN60204-1
Coast stop under the control of the MC in the main circuit
(2) An example of connection for operation in source mode (common: P24)
• In this connection, the PWR terminal is not used. This connection falls under Stop Category 0 defined in
IEC/EN60204-1.
Symbols Description
B1 VF-AS1
inverter
MCCB1 Circuit
breaker
MC1 Magnetic
condactor
MCCB2
Circuit breaker for control transformer
T1
Control transformer 400/200V (For 400V class only)
CP Circuit
protector
PB1
Push button switch (Run)
PB2
Push button switch (Stop/emergency stop)
Rs Control
relay
*1: Some inverters* are shipped with the PO and PA/+ terminals short-circuited with a shorting bar. (* 200V/45kW
class and lower and 400V/75kW class and lower)
*2:
To back up the inverter’s internal power supply that supplies control power, an external control power backup
device (CPS002Z - optional) is required. The optional control power backup device can be used with both 200V
and 400V classes.
*3: By default, the FL relay is set as a failure FL output relay.