E6581442
J-2
10
Selection of wiring equipment
No-fuse breaker
(MCCB)
Magnetic contactor
(MC)
Input current[A]
Without
Reactor
With
Reactor
Without
Reactor
With
Reactor
Voltage
class
Applicable
motor [kW]
Inverter model
Without
Reactor
With
Reactor
Rated current
[A]
Rated current
[A]
Operationl
current [A]
AC-1
Operationl
current [A]
AC-1
0.4 VFAS1-2004PL
3.5
2.1 5
5
25
25
0.75 VFAS1-2007PL 6.1 3.2 10
5
25
25
1.5
VFAS1-2015PL
11.5
6.4
15 10 25 25
2.2
VFAS1-2022PL
15
9.3
20 15 25 25
3.7/4.0
VFAS1-2037PL
26.0
15.5
30 30 32 25
5.5
VFAS1-2055PL
35
22.
5
50 40 40 25
7.5
VFAS1-2075PL
45
34.5
60 40 50 40
11
VFAS1-2110PM
-
53.5
- 75 - 80
15 VFAS1-2150PM
-
72 -
100 -
80
18.5 VFAS1-2185PM -
77 -
100 -
80
22 VFAS1-2220PM
-
88 -
125 -
125
30 VFAS1-2300PM
-
125 -
150 -
125
37 VFAS1-2370PM
-
140 -
175 -
250
45 VFAS1-2450PM
-
165 -
200 -
250
55 VFAS1-2550P -
200 -
250 -
275
200V
class
75 VFAS1-2750P -
270 -
350 -
350
0.75 VFAS1-4007PL 3.7 2.1
5
4
25
25
1.5
VFAS1-4015PL
5.8
3.8
10 6.3 25 25
2.2
VFAS1-4022PL
8.2
5.7
14 10 25 25
3.7/4.0
VFAS1-4037PL
14.0
8.7
18 14 25 25
5.5
VFAS1-4055PL
20.5
12.7
32 25 25 25
7.5
VFAS1-4075PL
27
16.3
32 25 32 25
11
VFAS1-4110PL
36.5
21.5
50 30 40 32
15
VFAS1-4150PL
48
33.5
60 40 50 40
18.5
VFAS1-4185PL
-
45.5
- 60 - 50
22 VFAS1-4220PL -
50 -
60 -
50
30 VFAS1-4300PL -
66 -
100 -
80
37 VFAS1-4370PL -
84 -
100 -
125
45 VFAS1-4450PL -
105 -
125 -
125
55 VFAS1-4550PL -
120 -
150 -
125
75 VFAS1-4750PL -
165 -
200 -
250
90 VFAS1-4900PC
-
170 -
200 -
250
110 VFAS1-4110KPC
-
200 -
250 -
275
132 VFAS1-4132KPC
-
240 -
300 -
315
160 VFAS1-4160KPC
-
290 -
350 -
350
200 VFAS1-4200KPC
-
360 -
500 -
500
220 VFAS1-4220KPC
-
395 -
500 -
500
280 VFAS1-4280KPC
-
495 -
700 -
700
355 VFAS1-4355KPC
-
637 -
1000 -
1000
400 VFAS1-4400KPC
-
709 -
1000 -
1000
400V
class
500 VFAS1-4500KPC
-
876 -
1200 -
1600
(*1): Selections for use of the Toshiba 4-pole standard motor with power supply voltage of 200V/400V-50Hz.
(*2): Choose the MCCB according to the power supply capacity.
For comply with UL and CSA standard, use the fuse certified by UL and CSA.
(*3): When using on the motor side during commercial-power supply operation, choose the MC with class AC-3 rated current
for the motor rated current.
(*4): Attach surge killers to the magnetic contactor and exciting coil of the relay.
(*5): In the case the magnetic contactor (MC) with 2a-type auxiliary contacts is used for the control circuit, raise the reliability
of the contact by using 2a-type contacts in parallel connection.
(*6): For 200V/55kW model and larger and 400V/90kW model and larger, be sure to install a DC reactor.