![Toshiba TOSVERT VF-AS1 Series Скачать руководство пользователя страница 156](http://html.mh-extra.com/html/toshiba/tosvert-vf-as1-series/tosvert-vf-as1-series_instruction-manual_424758156.webp)
E6581442
F-40
6
(1) Setting auto-tuning
This auto tuning function allows you to set the motor constant easily, which needs to be set when operating in auto
torque boost mode or vector control mode (
=
,
,
,
or
).
There are two parameters (
and
described below) for auto tuning. For the steps to be followed
when setting these parameters, see the flowchart on the previous page. This section provides an explanation of
and
.
[Parameter setting]
Title
Function
Adjustment range
Default setting
Auto-tuning 1
:No auto-tuning
:Initialize motor constant (
after execution)
:Continue operation continued after auto-tuning
(
after execution)
:Auto-tuning by input terminal signal(
after execution)
:Motor constant auto calculation (
after execution)
=
: Resets
(motor constant 1),
(motor constant 2),
(motor constant 3) and
(motor constant 4) to their factory default settings (constant of a Toshiba standard four-pole
motor with the same capacity as the inverter).
=
: Makes the inverter tune the motor constant, considering how the motor is connected, when it is
started for the first time after this setting is made. Connect the motor to the inverter in advance when
selecting this setting.
=
: Makes the inverter only tune the motor constant, unlike
=
. Connect the motor to the inverter
in advance when selecting this setting.
This function operates when "ST" signal and "Auto-tuning" signal became active.
(Use this setting if the machine cannot be started as-is after tuning for some reason on the part of the
machine.)
=
: If you select this setting after entering the information indicated on the motor nameplate (
(base
frequency),
(base frequency voltage),
(rated current of motor),
(rated speed of
rotation of motor)), the inverter will calculate the motor constant and set the parameters
through
automatically.
There is no need to connect the motor when making this setting.
[Parameter setting]
Title
Function
Adjustment range
Default setting
Auto-tuning 2
:Disabled
:Self-cooled motor
:Forced-air-cooled motor
Auto-tuning 2 refers to the function of adjusting the motor constant automatically, while estimating the increase in
the motor temperature.
If your inverter is equipped with a self-cooling fan (fan connected directly to the motor shaft), set
to
.
When using a motor with a cooling fan (forced air-cooling type), set
to
.
• Perform auto-tuning 2 along with auto-tuning 1.
• Perform auto-tuning when the motor is cold (temperature equal to the ambient temperature).
Precautions on auto-tuning 1
(1) The inverter is tuned automatically (auto-tuning 1
=
) when the inverter is started for the first
time after setup. During auto-tuning 1, which takes about 3 minutes from several seconds, the motor is
energized, although it is standing still. Noise may be produced by the motor during auto-tuning 1,
which, however, does not indicate that something is wrong with the inverter or the motor.
(2) Conduct auto-tuning 1 (
=
) only after the motor has been connected and operation
completely stopped.
If auto-tuning is conducted immediately after operation stops, the presence of a residual voltage may
result in abnormal tuning.
(3) Usually, auto-tuning terminates into 3 minutes from several seconds as each model. If an error occurs,
however, the inverter trips (display
) and no motor constant is set. For these motors, perform
manual tuning using (2) described below.
(4) It may not be possible to tune automatically special motors such as high-speed motor or high-slip
motor. For these motors, perform manual tuning using (2) described below.
(5) Provide cranes and hoists with sufficient circuit protection such as mechanical braking. Without
sufficient circuit protection, the result of insufficient motor torque during tuning could create the risk of
the machine stalling/failing.
(6) If auto-tuning is impossible or an auto-tuning error (
) is displayed, perform manual tuning with (2)
described below.
Precautions on vector control
Refer to Section 5.6 (9).