6
6. Extended parameters
Extended parameters are provided for sophisticated operation, fine adjustment and other special purposes.
Refer to Section 11, Table of parameters.
6.1 Input/output
parameters
6.1.1 Low-speed signal
: Low-speed signal output frequency
[Parameter setting]
Title
Function
Adjustment range
Default setting
Low-speed signal output frequency
~
Hz
Output frequency [Hz]
Time [s]
Low-speed signal output
P24-OUT1 terminals (Default setting)
P24-OUT2 terminals
FLA-FLB-FLC terminals
ON
OFF
Low-speed signal output: Inverted
ON
OFF
0
Set frequency
[Connection diagram (Sink logic)]
P24
OUT1 (or OUT2)
NO
CC
Ry
• Function
When the output frequency exceeds the setting of
an ON signal will be generated. This signal can be
used as an electromagnetic brake excitation/release signal.
Through the open collector terminal OUT1 or OUT2 (24Vdc-50mA [max.]).
• Output terminal setting
The low-speed signal (ON signal) output function has been assigned to the terminal OUT1 by default. This
setting must be changed to invert the polarity of the signal.
[Parameter setting]
Title
Function
Adjustment range
Setting value
Output terminal function selection
1(OUT1)
~
(ON signal) or
(OFF signal)
Note: To put out signals to OUT2, select the parameter
.