K-1
E6581442
11
11. Table of parameters
1. User parameter
*3 Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Vector control
Title
Communi
cation
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Speed
control
Torque
control
PM
control
*2
V/f
*1
Reference
-
Operation frequency of
operation panel
~
Hz
0.1/0.01
0.0
Enabled
●
/
●
●
/
●
●
●
3.
2
*1: V/f : Any setting of
=
,
,
*2: PM control :
=
setting *3: Sensorless vector : Any setting of
=
,
,
/ Vector with sensor : Any setting of
=
,
2. Basic parameter [1/4]
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Vector control
Title
Communi
cation
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Speed
control
Torque
control
PM
control
V/f Reference
- History
function
1/1
-
-
●
/
●
●
/
●
●
●
5.
1
0000
Automatic
acceleration/deceleration
0:Disabled
1:Automatic setting
2:Automatic setting (during acceleration only)
1/1 0
Disabled
●
/
●
-
●
●
5.
2
0001 Automatic
torque
boost
0:Disabled
1:Automatic torque boost + auto-tuning 1
2:Sensorless vector control 1+ auto-tuning 1
1/1 0
Disabled
●
/
●
-
●
●
5.
3
0040
Automatic function
setting
0:Disabled
1:Frequency setting by means of voltage
2:Frequency setting by means of current
3:Voltage/current switching from external terminal
4: Frequency setting on operation panel and operation by
means of terminals
5: Frequency setting and operation on operation panel
1/1 0
Disabled
●
/
●
●
/
●
●
●
5.
4
0003
Command mode
selection
0:Terminal input enabled
1:Operation panel input enabled (including LED/LCD
option input)
2:2-wire RS485 communication input
3:4-wireRS485 communication input
4:Communication option input
1/1 0
Disabled
●
/
●
●
/
●
●
●
5.
5
0004
Frequency setting mode
selection 1
1:VI/II (voltage/current input)
2:RR/S4 (potentiometer/voltage input)
3:RX (voltage input)
4:Operation panel input enabled (including LED/LCD
option input)
5:2-wire RS485 communication input
6:4-wire RS485 communication input
7:Communication option input
8:Optional AI1 (differential current input)
9:Optional AI2 (voltage/current input)
10:UP/DOWN frequency
11:Optional RP pulse input
12:Optional high-speed pulse input
13: - *1
1/1 2
Disabled
●
/
●
-
●
●
5.
5
*1: Unsupported option
Содержание TOSVERT VF-AS1 Series
Страница 238: ...E6581442 I 7 9 ...
Страница 261: ...E6581442 J 13 10 VFAS1 4200KPC 4280KPC VFAS1 4355KPC 4400KPC 4500KPC ...
Страница 321: ...E6581442 M 3 13 Continued overleaf ...