![Toshiba TOSVERT VF-AS1 Series Скачать руководство пользователя страница 209](http://html.mh-extra.com/html/toshiba/tosvert-vf-as1-series/tosvert-vf-as1-series_instruction-manual_424758209.webp)
E6581442
G-4
7
Table of setting of contact input terminal function
Parameter setting
Parameter setting
Positive
logic
Negative
logic
Function
Positive
logic
Negative
logic
Function
No function is assigned
Servo lock signal
F: Forward run command
Simple positioning (positioning loop)
R: Reverse run command
Integrating wattmeter display clear
ST: Standby
Trace back trigger signal
RES: Reset
Light-load high-speed operation
prohibitive signal
S1: Preset speed 1
No function assigned
S2: Preset speed 2
No function assigned
S3: Preset speed 3
No function assigned
S4: Preset speed 4
Binary data write
Jog run
Up/down frequency (up)
*
1
Emergency stop
Up/down frequency (down)
*
1
DC braking
Up/down frequency (clear)
Acceleration/deceleration switching 1 *2
Dancer correction OFF
Acceleration/deceleration switching 2 *2
No function assigned
V/f switching signal 1 *2
Forward/reverse selection
V/f switching signal 2 *2
Run/stop command
*
3
Torque limit switching signal 1 *2
Commercial power/INV switching
Torque limit switching signal 2 *2
Frequency reference priority switching
PID control OFF selection
VI/II terminal priority
Pattern operation group 1
Command terminal board priority
Pattern operation selection 2
Permission of parameter editing *5
Pattern operation continuation signal
Speed/Torque switching
Pattern operation trigger signal
No function assigned
External thermal error
No function assigned
Communication priority cancel
No function assigned
HD operation retention
No function assigned
PID differentiation/integration clear
Rapidest deceleration command
PID forward/reverse switching
Preliminary excitation
*
4
Forced continuous operation
Braking request
Specified speed operation
No function assigned
Acceleration/deceleration suspend signal
Brake answer back input
Power failure synchronized signal
No function assigned
My function RUN signal
Traverse permission signal
Auto-tuning signal
Speed gain switching
*1: Valid when
(Frequency setting mode selection 1) is set at
(Up/down frequency).
The frequency setting range is between =
~
(Upper limit frequency). The acceleration/deceleration time with respect
to the frequency setting remains
/
, unless switching between acceleration and deceleration is performed.
*2: To switch acceleration/deceleration pattern, V/f pattern, torque limit 1~4, give the following signals to switching functions.
Switching signal 1
Switching signal 2
Acceleration/deceleration1, V/f 1, torque limit 1
OFF
OFF
Acceleration/deceleration2, V/f 2, torque limit 2
ON
OFF
Acceleration/deceleration3, V/f 3, torque limit 3
OFF
ON
Acceleration/deceleration4, V/f 4, torque limit 4
ON
ON
*3: If
,
(F: Forward run command) or
,
(R: Reverse run command) is assigned at the same time, this function has a
priority.
*4: After the motor slows down and comes to a full stop at a pre-excitation command, the motor is set free momentarily to
bring it into a pre-excitation state.
This function should not be used when
is set to
or
. Or the inverter might malfunction.
*5: Do not set the function " Permission of parameter editing" into the parameter
~
(without option)
and
~
. If it is set, cannot reset the setting.