E6581442
11
K-24
[25] Protection functions [2/2]
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Vector control
Title
Communi
cation
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Speed
control
Torque
control
PM
control V/f Constant Reference
0622
Abnormal speed detection time
0.01~100.0 sec.
0.01/0.01
0.01
Enabled
●
/
●
●
/
●
●
●
6. 33. 13
0623
Overspeed detection frequency
upper band
0.0:Disabled, 0.1~30.0Hz
0.1/0.01
0.0
Enabled
●
/
●
●
/
●
●
●
6. 33. 13
0624
Overspeed detection frequency
lower band
0.0:Disabled, 0.1~30.0Hz
0.1/0.01
0.0
Enabled
●
/
●
●
/
●
●
●
6. 33. 13
0625
Undervoltage detection level
50~79%, 80: (auto mode)
1/1
80 Disabled
●
/
●
●
/
●
●
●
6. 33. 15
0626
Overvoltage limit operation level 100~150%
1/1
134 Disabled
●
/
●
-
●
●
6. 14. 2
0627
Undervoltage trip selection
0:Disabled
1:Enabled
1/1 0
Disabled
●
/
●
●
/
●
●
●
6. 33. 15
0628
Undervoltage (trip alarm)
detection time
0.01~10.00 sec.
0.01/0.01
0.03
Disabled
●
/
●
●
/
●
●
●
6. 33. 15
0629
Regenerative power ride-through
control level
55~100% 1/1
75
Disabled
●
/
●
●
/
●
●
●
6. 33. 16
0630
Braking answer waiting time
0.0:Disabled, 0.1~10.0 sec.
0.1/0.1
0.0
Enabled
●
/
●
-
-
-
6. 33. 17
0631 Temperature
detection
0:Standard (150%-60 sec.)
1:Estimation of temperature
1/1 0
Disabled
- - - -
5.
14
0633
VI/II analog input wire breakage
detection level
0:None
1~100%
1/1 0
Enabled
●
/
●
●
/
●
●
●
6. 33. 18
0634
Annual average ambient
temperature (calculation for part
replacement alarms)
1:-10~+10°C
2:+11~+20°C
3:+21~+30°C
4:+31~+40°C
5:+41~+50°C
6:+51~+60°C
1/1 3
Enabled
●
/
●
●
/
●
●
●
6. 33. 19
0635
Rush current suppression relay
activation time
0.0~2.5 sec.
0.1/0.1
0.0
Disabled
●
/
●
●
/
●
●
●
6. 33. 20
0637 PTC1
thermal
selection
0:Deselect
1:Select
1/1 0
Disabled
●
/
●
●
/
●
●
●
*1
0638 PTC2
thermal
selection
0:Deselect
1:Select
1/1 0
Disabled
●
/
●
●
/
●
●
●
*1
0639
Braking resistance overload
time (10 times of rated torque)
0.1~600.0 sec.
0.1/0.1
5.0
Disabled
●
/
●
●
/
●
●
●
5.
19
0640
Step-out detection current level
(for PM motors)
10~150 1/1
100
Disabled
-
-
●
- 6.
29
0641
Step-out detection time (for PM
motors)
0.0:Not detect
0.1~25.0
0.1/0.1 0.0
Disabled
-
-
●
- 6.
29
0643
Brake-equipped motor restart
condition selection
0:Default (no waiting time for frequencies of 10Hz
and less)
1:Conditional (no waiting time for frequencies of
20Hz and less)
1/1 0
Disabled
●
/
●
●
/
●
●
●
6. 33. 23
0647
Control power supply backup
option failure monitoring
0:Control power supply not backed up
1:Control power supply backed up (alarm in the
event of a failure)
2:Control power supply backed up (tripping in the
event of a failure)
1/1 0
Disabled
●
/
●
●
/
●
●
●
6. 33. 24
*1:
For details, refer to Instruction Manual (E6581339) specified in Section 6.42.