E6581442
11
K-12
[12] Tripless intensification setup [2/2]
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Vector control
Title
Communi
cation
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Speed
control
Torque
control
PM
control
V/f Reference
0307
Base frequency voltage
selection
(correction of supply voltage)
0:Without voltage compensation (limitless output voltage)
1:With voltage compensation (limitless output voltage)
2:Without voltage compensation (limited output voltage)
3:With voltage compensation (limited output voltage)
1/1 0
Disabled
Parameter is changeable, but fixed to
"with voltage compensation" internally.
When
is set to 0 or 1, fixed at
1 internally.
When
is set to 2 or 3, fixed at
3 internally.
●
6. 14. 3
0308
Dynamic braking resistance
0.5~1000
Ω
0.1/0.1
*1
Disabled
●
/
●
●
/
●
●
●
5. 19
0309
Allowable continuous braking resistance 0.01~600.0kW
0.01/0.01
*1
Disabled
●
/
●
●
/
●
●
●
5. 19
0310
Non-stop control time/deceleration
time during power failure
0.1~320.0 sec.
0.1/0.1
2.0
Enabled *3/
Disabled
●
/
●
-/-
●
●
5. 18. 2
0311
Reverse-run prohibition
selection
0:Permit all, 1:Prohibit reverse run
2:Prohibit forward run
1/1 0
Disabled
●
/
●
●
/
●
●
●
6. 14. 4
0312 Random mode
0:Disabled, 1:Enabled
1/1
0
Disabled
●
/
●
●
/
●
●
●
5.
17
0313
Output voltage waveform
selection *4
0:PWM carrier frequency control 1
1:PWM carrier frequency control 2
1/1
0
Disabled
●
/
●
●
/
●
●
●
6. 14. 5
0316
Carrier frequency control mode
selection
0:Not decrease carrier frequency automatically
1:Decrease carrier frequency automatically
2:Not decrease carrier frequency automatically,
400V class supported
3:Decrease carrier frequency automatically, 400V
class supported
4:Not decrease carrier frequency automatically,
with sinusoidal filter
5:Decrease carrier frequency automatically, with
sinusoidal filter
1/1 1
Disabled
●
/
●
●
/
●
●
●
5.
17
0317
Synchronized deceleration time
(time elapsed between start of
deceleration to stop)
0.1~6000 sec.
0.1/0.1 *2
2.0
Enabled
●
/
●
-/-
●
●
5. 18. 2
0318
Synchronized acceleration time
(time elapsed between start of
acceleration to achievement of
specified speed)
0.1~6000 sec.
0.1/0.1 *2
2.0
Enabled
●
/
●
-/-
●
●
5. 18. 2
0319
Regenerative over-excitation
upper limit
100~160% 1/1
140
Disabled
●
/
●
●
/
●
-
●
6. 14. 2
This parameter moves to a fundamental parameter. *1: Default values vary depending on the capacity.
See the table of K-48.
*2: Changing the parameter
enables to set to 0.01 sec. (adjustment range: 0.01~600.0 sec.).
*3: Although the setting can be written into memory if
is set to
(power ride-through control), it cannot be written if
is set to
(deceleration stop during a power failure).
*4:
is available for VFAS1-2550P, VFAS1-4900PC and above.
[13] Drooping control
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Vector control
Title
Communi
cation
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Speed
control
Torque
control
PM
control
V/f Reference
0320
Drooping gain
0.0~100.0% (Enabled if
=3, 4, 7 or 8)
0.1/0.1 0.0
Enabled *1
●
/
●
- - - 6.
15
0321 Speed at drooping gain 0%
0.0~320.0Hz (Enabled if
=3, 4, 7 or 8)
0.1/0.01
0.0
Enabled
●
/
●
- - - 6.
15
0322 Speed at drooping gain
0.0~320.0Hz (Enabled if
=3, 4, 7 or 8)
0.1/0.01
0.0
Enabled
●
/
●
- - - 6.
15
0323
Drooping insensitive torque
0~100% (Enabled if
=3, 4, 7 or 8)
1/1
10
Enabled
●
/
●
- - - 6.
15
*1: Drooping gain can be changed within a range of 0.1 to 100.0% during operation. When changing the setting to 0.0 (no drooping) or 0.0, stop operation.
Содержание TOSVERT VF-AS1 Series
Страница 238: ...E6581442 I 7 9 ...
Страница 261: ...E6581442 J 13 10 VFAS1 4200KPC 4280KPC VFAS1 4355KPC 4400KPC 4500KPC ...
Страница 321: ...E6581442 M 3 13 Continued overleaf ...