E6581611
K-22
11
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0711
Status monitor 1
-
-
2
6.34.6
8.2.1
8.3.2
0712
Status monitor 2
-
-
1
0713
Status monitor 3
-
-
3
0714
Status monitor 4
-
-
4
0715
Status monitor 5
-
-
5
0716
Status monitor 6
-
-
6
0717
Status monitor 7
-
-
27
0718
Status monitor 8
-
-
0: Output frequency (Hz/free unit)
1: Output current (%/A)
2: Frequency command value
(Hz/free unit)
3: Input voltage (DC detection) (%/V)
4: Output voltage (command value) (%/V)
5: Input power (kW)
6: Output power (kW)
7: Torque (%)
8: -
9: Motor cumulative load factor
10: Inverter cumulative load factor
11: PBR (Braking resistor) cumulative
load factor
12: Stator frequency (Hz/free unit)
13: VIA input value (%)
14: VIB input value (%)
15 to 17: -
18: Arbitrary code from communication
19: -
20: VIC input value (%)
21: Pulse train input value (pps)
22: -
23: PID feedback value (Hz/free unit)
24: Integral input power (kWh)
25: Integral output power (kWh)
26: Motor load factor (%)
27: Inverter load factor (%)
28: Inverter rated current (A)
29: FM output value (%)
30: Pulse train output value (pps)
31: Cumulative power on time (100
hours)
32: Cumulative fan operation time
(100 hours)
33: Cumulative operation time (100
hours)
34: Number of starting (10000 times)
35: Forward number of starting
(10000 times)
36: Reverse number of starting
(10000 times)
37: Number of trip (times)
38, 39: -
40: Inverter rated current (Carrier
frequency corrected)
41 to 51: -
52: Frequency command value /
output frequency (Hz/free unit)
0
0719
Selection of
operation
command clear
-
-
0: Clear at coast stop and retained at
moff
.
1: Retained at coast stop and
moff
.
2: Clear at coast stop and
moff
.
3: 2+ clear when
cmod
is changed
1
6.34.8
0720
Initial extension
panel display
selection
-
-
0-52 (Same as
f710
) 0
6.
34.5
0721
Panel stop pattern
-
-
0: Deceleration stop
1: Coast stop
0
6.
34.9
0724
Operation
frequency setting
target by setting
dial
-
-
0: Panel frequency (
)
1: Panel frequency (
) + Preset
speed frequency
0 5.7
Содержание Q9 Plus ASD
Страница 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Страница 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Страница 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Страница 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Страница 429: ......
Страница 430: ......