E6581611
E-11
5
[Using a VF motor (motor for use with inverter)]
Setting of electronic thermal protection characteristics selection
Setting value
Overload protection
Overload stall
valid invalid
valid valid
invalid invalid
invalid valid
VF motors (motors designed for use with inverters) can be used in frequency ranges lower than those
for standard motors, but their cooling efficiency decreases at frequencies below 6Hz.
Setting of motor electronic thermal protection level 1
(Same as
f173
)
If the capacity of the motor is smaller than the capacity of the inverter, or the rated current of the motor
is smaller than the rated current of the inverter, adjust the electronic thermal protection level 1
so
that it fits the motor's rated current.
* If the indications are in percentages (%), then 100% equals the inverter's rated output current (A).
×1.0
Output frequency (Hz)
Output current reduction factor [%]/[A]
0
Note) The start level for motor overload reduction is fixed at 6 Hz.
6Hz
×0.6
2) Motor 150%-overload detection time
f607
Parameter
f607
is used to set the time elapsed before the motor trips under a load of 150% (overload trip
2
) within a range of 10 to 2400 seconds.
3) Inverter overload detection method
f631
As this function is set to protect the inverter unit, this function cannot be turned off by parameter setting.
The inverter overload detection method can be selected using parameter
f631
(Inverter overload
detection method).
[Parameter setting]
Title
Function
Adjustment range
Default setting
f631
Inverter overload detection method
0: 150%-60s (120%-60s)
1: Temperature estimation
0
If the inverter overload trip function (
ol1
) is activated frequently, this can be improved by adjusting the stall
operation level
f601
downward or increasing the acceleration time
acc
or deceleration time
dec
.
Содержание Q9 Plus ASD
Страница 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Страница 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Страница 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Страница 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Страница 429: ......
Страница 430: ......