E6581611
K-16
11
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0511 Deceleration
time
3
s
0.1/0.1
0.0-3600 (360.0) *8
10.0
6.27.2
0512 Acceleration/decel
eration 3 pattern
- -
0:
Linear
1: S-pattern 1
2: S-pattern 2
0
0513 Acceleration/decel
eration 2 and 3
switching
frequency
Hz 0.1/0.01
0.0
(disabled)
0.1-
0.0
0515 Deceleration
time
at emergency stop
s
0.1/0.1
0.0-3600 (360.0) *8
10.0
6.29.4
0519 Setting
of
acceleration/decel
eration time unit
- -
0:
-
1: 0.01s unit (after execution: 0)
2: 0.1s unit (after execution: 0)
0 5.2
6.27.2
0590 Shock
monitoring -
- 0:
Disabled
1: Current detection
2: Torque detection
0
6.28
0591 Shock
monitoring
trip/alarm
selection
- -
0: Alarm only
1: Tripping
0
0592 Shock
monitoring
detection direction
selection
-
-
0: Over-current / torque detection
1: Low-current / torque detection
0
0593 Shock
monitoring
detection level
% 1/1
0-250
150
0595 Shock
monitoring
detection time
s 0.1/0.1
0.0-10.0
0.5
0596 Shock
monitoring
detection
hysteresis
% 1/1
0-100
10
0597 Shock
monitoring
detection start
waiting time
s 0.1/0.1
0.0-300.0
0.0
0598 Shock
monitoring
detection action
selection
-
-
0: During operation
1: During operation (except
acceleration / deceleration)
0
*8: These parameters can be changed to 0.01s unit by setting
f519
=
1
.
Содержание Q9 Plus ASD
Страница 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Страница 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Страница 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Страница 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Страница 429: ......
Страница 430: ......