6.19.7 Reverse-run
prohibition
f311
: Reverse-run prohibition
•
Function
This function prevents the motor from running in the forward or reverse direction when it receives the
wrong operation signal.
[Parameter setting]
Title
Function
Adjustment range
Default setting
f311
Reverse-run prohibition
0: Forward/reverse run permitted
1: Reverse run prohibited
2: Forward run prohibited
0
6.20 Drooping
control
f320
: Droop gain
f323
: Droop insensitive torque band
f324
: Droop output filter
•
Function
Drooping control has the function to prevent loads from concentrating at a specific motor because of
a load imbalance when multiple inverters are used to operate one machine.
These parameters are used to allow the motor to “slip” according to the load torque current. The
insensitive torque band and the gain can be adjusted using these parameters.
[Parameter setting]
Title
Function
Adjustment range
Default setting
f320
Droop gain
0.0-100.0 (%)
0.0
f323
Droop insensitive torque band
0-100 (%)
10
f324
Droop output filter
0.1-200.0
100.0