E6581611
F-131
6
6.34.8 Cancel the operation command
f719
: Selection of operation command clear
•
Function
This parameter allows you to select operation command retained or operation command canceled,
when coast stop occurs due to standby terminal function (ST) or coast stop command terminal function,
and when under voltage in main circuit alarm occurs, during panel operation or RS485 communication
operation.
Parameter setting
At coast stop
Under voltage in main circuit alarm occurrence
=
Operation command canceled
Operation command retained
=
Operation command retained
=
Operation command canceled
Operation command retained :
Inverter restarts due to canceling coast stop at coast stop.
Inverter restarts due to supply power source again when the under voltage in main circuit alarm (
)
occurs.
Operation command canceled :
Inverter doesn’t restart after coast stop or occurring the under voltage in main circuit alarm (
).
Press RUN key to operate again in panel operation.
Switch to ON the operation command in RS485 communication operation.
Title
Function
Adjustment range
Default setting
f719
Selection of operation
command clear
0: Clear at coast stop and retained at
moff
.
1: Retained at coast stop and
moff
.
2: Clear at coast stop and
moff
.
3: 2+ clear when
cmod
is changed
1
[Setup example of input terminal]
When it is assigned to the RES terminal.
Title
Function
Adjustment range
Setting
f113
Input terminal selection 3A
(RES)
0-203
6: ST (Standby)
f113
Input terminal selection 3A
(RES)
0-203
96: FRR (Coast stop command)
Setting value 7, 97 are reverse signal.
Содержание Q9 Plus ASD
Страница 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Страница 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Страница 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Страница 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Страница 429: ......
Страница 430: ......