E6581611
F-53
6
Operation example : Remote mode (
cmod
=
0
: (Terminal block))
Remote mode
Local mode
ON
OFF
ON
OFF
ON
OFF
Key
Output
frequency
F-CC
Internal
operation
command
Local mode
Remote mode
ON
OFF
ON
OFF
ON
OFF
Key
Output
frequency
F-CC
Internal
operation
command
Set frequency at
Remote mode
Setting frequency and start/stop
status are moved to Local mode
when switching from Remote
mode to Local mode.
Motor runs continuously for the
case described on the left.
When switching from Local
mode to Remote mode, setting
frequency and start/stop status
are determined by Remote
mode status.
For the case described on the
left, the motor runs continuously
because the Remote mode is
“run” status.
,
To prevent from moving the setting frequency and start/stop status of Remote mode to Local
mode, set
to “
”(Disabled). In this case, key is effective only while stopping.
EASY
EASY
EASY