7) Operating a permanent magnet motor
Setting of V/F control mode selection
to
(PM motor control)
Permanent magnet motors (PM motors) that are light, small in size and highly efficient, as compared to
induction motors, can be operated in sensor-less operation mode.
Note that this feature can be used only for specific motors. For more information, contact your Toshiba
distributor.
8) Setting of V/f characteristic arbitrarily
Setting of V/f control mode selection
pt
to
7
(V/f 5-point setting)
In this mode, the base frequency and the base frequency voltage for the V/f control need to be set to operate
the motor while switching a maximum of 5 different V/f characteristics.
[Parameter setting]
Title
Function
Adjustment range
Default setting
V/f 5-point setting VF1 frequency
~
(Hz)
V/f 5-point setting VF1 voltage
~
(%) *
V/f 5-point setting VF2 frequency
~
(Hz)
V/f 5-point setting VF2 voltage
~
(%) *
V/f 5-point setting VF3 frequency
~
(Hz)
V/f 5-point setting VF3 voltage
~
(%) *
V/f 5-point setting VF4 frequency
~
Hz
V/f 5-point setting VF4 voltage
~
(%) *
V/f 5-point setting VF5 frequency
~
(Hz)
V/f 5-point setting VF5 voltage
~
(%) *
* 100% value is 200V for 240V class, and 400V for 500V class.
Base frequency
voltage 1
O
u
tput
vol
ta
ge
[V]/[%]
Output frequency [Hz]
Base frequency 1
0
VF1
VF2
VF3
VF4
VF5
V/f 5-point setting
Note 1: Restrict the value of torque to boost (
vb
) to 3% or so. Boosting the torque too much may impair the
linearity between points.
Note 2: Please note if the inclination of each V/f is too high (exceeding 8.25%/Hz),
a
-
02
(Points setting alarm 2)
will occur.
9) Cautions for vector control
Содержание Q9 Plus ASD
Страница 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Страница 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Страница 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Страница 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Страница 429: ......
Страница 430: ......