E6581611
I-4
9
(2) Use shielded power cables, such as inverter output cables, and shielded control cables. Route the cables and
wires so as to minimize their lengths. Keep a distance between the power cable and the control cable and
between the input and output wires of the power cable. Do not route them in parallel or bind them together.
Instead, if necessary, cross at right angle.
(3) It is more effective in limiting the radiation noise to install the inverter in a sealed steel cabinet. Using wires as
thick and short as possible, earth the metal plate and the control panel securely with a distance kept between
the earth cable and the power cable.
(4) Route the input and output wires apart as far as possible from each other.
(5) To suppress radiation noise from cables, ground all shielded cables through a noise cut plate.
It is effective to earth shielded cables in the vicinity of the inverter and cabinet (within a radius of 10cm from
each of them). Inserting a ferrite core in a shielded cable is even more effective in limiting the radiation noise.
(6) To further limit the radiation noise, insert a zero-phase reactor in the inverter output line and insert ferrite cores
in the earth cables of the metal plate and cabinet.