6.29.5 Output phase failure detection
f605
: Output phase failure detection selection
•
Function
This parameter detects inverter output phase failure. If the phase failure status persists for one
second or more, trip occurs and the failure signal FL will be activated. Trip information
epho
will be
displayed.
Set
f605
to
5
to open the motor-inverter connection by switching commercial power operation to
inverter operation.
Detection errors may occur for special motors such as high-speed motors.
f605
=
0
: No tripping. (Failure signal FL not activated)
f605
=
1
: With the power on, the output phase failure will be detected when the first operation starts.
The inverter will trip if the phase failure status persists for one second or more. (Failure signal FL
activated)
f605
=
2
: The inverter checks for output phase failures every time the operation starts. The inverter will trip
if the phase failure status persists for one second or more. (Failure signal FL activated)
f605
=
3
: The inverter checks for output phase failures during operation. The inverter will trip if the phase
failure status persists for one second or more. (Failure signal FL activated)
f605
=
4
: The inverter checks for output phase failures at the start and during operation. The inverter will
trip if the phase failure status persists for one second or more. (Failure signal FL activated)
f605
=
5
: If the inverter detects an all-phase failure, it will restart on completion of reconnection. The
inverter does not check for output phase failures when restarting after a momentary power failure.
(Failure signal FL not activated)
[Parameter setting]
Title
Function
Adjustment range
Default setting
f605
Output phase failure detection
selection
0: Disabled
1: At start-up (only one time after
power on)
2: At start-up (each time)
3: During operation
4: At start-up + during operation
5: Detection of cutoff on output side
0
Note1) A check for output phase failures is made during auto-tuning, regardless of the setting of this parameter.
Note2) When parameter
pt
=
5
or
6
is selected,
f605
=
3
to
5
do not work.
Содержание Q9 Plus ASD
Страница 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Страница 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Страница 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Страница 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Страница 429: ......
Страница 430: ......