E6581611
K-19
11
Output
parameters
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0667 Integral
input
power pulse
output unit
- -
0: 0.1kWh
1: 1kWh
2: 10kWh
3: 100kWh
1
6.33.1
0668 Integral
input
power pulse
output width
s 0.1/0.1
0.1-1.0
0.1
0669
Logic output/pulse
train output
selection (OUT)
-
-
0: Logic output
1: Pulse train output
0
6.33.2
0676
Pulse train output
function selection
(OUT)
- -
0: Output
frequency
1: Output current
2: Frequency command
value
3: Input voltage (DC detection)
4: Output voltage (command value)
5: Input power
6: Output power
7: Torque
8: -
9: Motor cumulative load factor
10: Inverter cumulative load factor
11: PBR (Braking resistor) cumulative
load factor
12: Stator frequency
13: VIA input value
14: VIB input value
15: Fixed output 1
(output current 100% equivalent)
16: Fixed output 2
(output current 50% equivalent)
17: Fixed output 3
(Other than the output current)
18: Communication data
19: -
20: VIC input value
21, 22: -
23: PID feedback value
0
0677 Maximum
numbers
of pulse train
output
kpps
0.01/0.01 0.50-2.00
0.80
0678
Pulse train output
filter
ms 1/1
2-1000
64
0679
Pulse train input
filter
ms 1/1
2-1000
2 6.10.5
0681 Analog
output
signal selection
-
-
0: Meter option (0 to 1 mA)
1: Current (0 to 20 mA) output
2: Voltage (0 to 10 V) output
0 5.1
6.33.3
0684 Analog
output
filter
ms 1/1
2-1000
2
0691 Inclination
characteristic of
analog output
-
-
0: Negative inclination (downward
slope)
1: Positive inclination (upward slope)
1
0692
Analog output bias
%
0.1/0.1
-1.0
-
+100.0 0.0
0693 Factory
specific
coefficient 6E
- -
-
-
*
3
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.
Содержание Q9 Plus ASD
Страница 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Страница 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Страница 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Страница 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Страница 429: ......
Страница 430: ......