E6581611
K-17
11
Protection
parameters
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0601 Stall
prevention
level 1
%
(A)
1/1
10-199,
200 (disabled)
150 6.29.2
0602
Inverter trip
retention selection
-
-
0: Cleared with power off
1: Retained with power off
0
6.29.3
0603 Emergency
stop
selection
-
-
0: Coast stop
1: Deceleration stop
2: Emergency DC braking
3: Deceleration stop (
f515
)
4: Quick deceleration stop
5: Dynamic quick deceleration stop
0
6.29.4
0604
DC braking time
during emergency
stop
s 0.1/0.1
0.0-20.0 1.0
0605
Output phase
failure detection
selection
-
-
0: Disabled
1: At start-up (only one time after
power on)
2: At start-up (each time)
3: During operation
4: At start-up + during operation
5: Detection of cutoff on output side
0
6.29.5
0607 Motor
150%
overload detection
time
s 1/1
10-2400
300 5.6
6.29.1
0608
Input phase failure
detection selection
- -
0:
Disabled
1: Enabled
1
6.29.6
0609 Small
current
detection
hysteresis
% 1/1
1-20
10
0610 Small
current
trip/alarm
selection
- -
0:
Alarm
only
1: Tripping
0
0611 Small
current
detection current
%
(A)
1/1 0-150
0
0612 Small
current
detection time
s 1/1
0-255
0
6.29.7
0613 Detection
of
output short-circuit
at start-up
-
-
0: Each time (standard pulse)
1: Only one time after power on
(standard pulse)
2: Each time (short pulse)
3: Only one time after power on
(short pulse)
0
6.29.8
0614 Ground
fault
detection selection
- -
0: Disabled
1: Enabled
1
6.299
0615 Over-torque
trip/alarm
selection
- -
0:
Alarm
only
1: Tripping
0
0616 Over-torque
detection level
%
1/0.01 0
(disabled)
1-250
150
0618 Over-torque
detection time
s 0.1/0.1
0.0-10.0
0.5
6.29.10
0619 Over-torque
detection
hysteresis
% 1/1
0-100
10
0620 Cooling
fan
ON/OFF control
-
-
0: ON/OFF control
1: Always ON
0
6.29.11
0621 Cumulative
operation time
alarm setting
100
hours
0.1/0.1
(=10 hours)
0.0-999.0 876.0
6.29.12
0625
Factory specific
coefficient 6A
- -
-
- *3
0626 Over-voltage
stall
protection level
%
1/1 100-150
*2
6.19.4
6.19.5
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.
Содержание Q9 Plus ASD
Страница 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Страница 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Страница 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Страница 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Страница 429: ......
Страница 430: ......