E6581611
F-144
6
Title
Function
Adjustment range
Default setting
f910
Step-out detection current level
1 - 150 (%)
100
f911
Step-out detection time
0.00: No detection
0.01
-
2.55 (s)
0.00
f912
q-axis inductance
0.01-650.0 (mH)
10.00
f913
d-axis inductance
0.01-650.0 (mH)
10.00
Factory specific coefficient 9L
- -
⇒
Refer to section 6.25.2 about setting motor constants.
Note 1: When using an PM motor, consult your Toshiba dealer, since the inverter is not compatible with all
types of PM motors.
Note 2: The inverter may fail to detect step-out in some cases, because it uses an electrical method to detect
step-out. To avoid detection failures, you are recommended to install a mechanical step-out detector.
6.40 Traverse
function
f980
: Traverse selection
f981
: Traverse acceleration time
f982
: Traverse deceleration time
f983
: Traverse step
f984
: Traverse jump step
⇒
Refer to “Traverse control Instruction Manual : E6581877” for details.