E6581611
F-124
6
6.34 Operation panel parameter
6.34.1 Prohibition of key operations and parameter settings
f700
: Parameter protection selection
f730
: Panel frequency setting prohibition (
fc
)
f731
: Disconnection detection of extension panel
f732
: Local/remote key prohibition of extension panel
f733
: Panel operation prohibition (RUN key)
f734
: Panel emergency stop operation prohibition
f735
: Panel reset operation prohibition
f736
:
cmod
/
fmod
change prohibition during operation
f737
: All key operation prohibition
f738
: Password setting (
f700
)
f739
: Password verification
•
Function
These parameters allow you to prohibit or allow operation of the RUN and STOP keys on the
operation panel and the change of parameters. Using these parameters, you can also prohibit
various key operations. Lock parameters with a password to prevent configuration.
[Parameter setting]
Title
Function
Adjustment range
Default setting
f700
Parameter protection selection
0: Permitted
1: Writing prohibited (Panel and
extension panel)
2: Writing prohibited (1 + RS485
communication)
3: Reading prohibited (Panel and
extension panel)
4: Reading prohibited (3 + RS485
communication)
0
f730
Panel frequency setting prohibition
(
fc
)
0: Permitted, 1: Prohibited
0
Disconnection detection of extension
panel
0: Permitted, 1: Prohibited
0
f732
Local/remote key prohibition of
extension panel
0: Permitted, 1: Prohibited
1
f733
Panel operation prohibition
(RUN key)
0: Permitted, 1: Prohibited
0
Содержание Q9 Plus ASD
Страница 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Страница 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Страница 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Страница 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Страница 429: ......
Страница 430: ......