10. Peripheral devices
Warning
Mandatory
action
When using switchgear for the inverter, it must be installed in a cabinet.
Failure to do so can lead to risk of electric shock.
Be Grounded
Ground must be connected securely.
If the ground is not securely connected, it could lead to electric shock or fire.
10.1 Selection of wiring materials and devices
Selection of wire size
Wire size (mm²)
Note 4)
Power circuit
Note 1) Note 5)
Input Output
DC Reactor (Optional)
without DCL
with DCL
Voltage
class
Applicable
motor
(kW)
IEC
Compliant
For Japan
*1
IEC
Compliant
For Japan
*1
IEC
Compliant
For Japan
*1
IEC
Compliant
For Japan
*1
0.4 1.5 2.0 1.5 2.0 1.5 2.0 1.5 2.0
0.75 1.5 2.0 1.5 2.0 1.5 2.0 1.5 2.0
1.5 1.5 2.0 1.5 2.0 1.5 2.0 1.5 2.0
2.2 2.5 2.0 1.5 2.0 1.5 2.0 1.5 2.0
4.0 4.0 2.0 2.5 2.0 2.5 2.0 4.0 2.0
5.5 10 5.5 4.0 2.0 6.0 3.5 6.0 3.5
7.5 16 8.0 6.0 3.5 10 3.5 10 5.5
11 25 14 10 5.5 16 8.0 16 8.0
15 35 22 16 14 25 14 25 14
3 phase
240V
class
18.5 50 22 25 14 35 14 35 22
0.2 1.5 2.0 1.5 2.0 1.5 2.0 1.5 2.0
0.4 1.5 2.0 1.5 2.0 1.5 2.0 1.5 2.0
0.75 1.5 2.0 1.5 2.0 1.5 2.0 1.5 2.0
1.5 2.5 2.0 2.5 2.0 1.5 2.0 2.5 2.0
2.2 4.0 2.0 4.0 2.0 1.5 2.0 4.0 2.0
1 phase
240V
class
3.0 4.0 2.0 4.0 2.0 1.5 2.0 4.0 2.0
0.4 1.5 2.0 1.5 2.0 1.5 2.0 1.5 2.0
0.75 1.5 2.0 1.5 2.0 1.5 2.0 1.5 2.0
1.5 1.5 2.0 1.5 2.0 1.5 2.0 1.5 2.0
2.2 1.5 2.0 1.5 2.0 1.5 2.0 1.5 2.0
4.0 2.5 2.0 1.5 2.0 1.5 2.0 1.5 2.0
5.5 4.0 2.0 1.5 2.0 2.5 2.0 2.5 2.0
7.5 6.0 3.5 2.5 2.0 2.5 2.0 4.0 2.0
11 10 5.5 4.0 2.0 6.0 3.5 6.0 3.5
15 16 8.0 6.0 3.5 10 3.5 10 5.5
3 phase
500V
class
18.5 16 8.0 10 5.5 10 5.5 16 8.0
Содержание Q9 Plus ASD
Страница 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Страница 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Страница 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Страница 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Страница 429: ......
Страница 430: ......