E6581611
F-115
6
6.30 Forced fire-speed control function
f650
: Forced fire-speed control selection
f294
: Preset-speed frequency 15
•
Function
With forced fire-speed control, operate the motor at the specified frequency in case of an emergency.
Two kinds of operation are selectable by assignment of input terminal function.
(1) Input terminal function 56 (FORCE) : Input signal is retained once signal is ON.
Motor runs at the speed set by the parameter “
f294
”.
Motor is forced to operate in case of light failure.
Note: This case needs to power off in order to stop
(2) Input terminal function 58 (FIRE) : Input signal is retained once signal is ON.
Motor runs at the speed set by the parameter “
f294
”.
Note: In either case, power terminal should be off in order to stop.
[Parameter setting]
Title
Function
Adjustment range
Default setting
f650
Forced fire-speed control selection
0: Disabled
1: Enabled
0
f294
Preset-speed frequency 15
ll-ul
(Hz)
0.0
[Setup example of input terminal]
When the terminal “RES” is assigned.
Title
Function
Adjustment range
Setting value
f113
Input terminal selection 3A (RES)
0 - 203
56 ( Forced run operation )
or
58 ( Fire speed operation )
Each setting value 57, 59 are reverse signal.
+
“
fire
” and output frequency are blinking during forced run operation and fire-speed operation.
Содержание Q9 Plus ASD
Страница 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Страница 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Страница 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Страница 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Страница 429: ......
Страница 430: ......