E6581611
E-15
5
■
=
(Variable torque characteristic),
=
(Temperature estimation)
This parameter adjusts automatically overload protection, predicting the inverter internal temperature rise.
(diagonally shaded area in the figure below)
Note 1: The rated output current of inverter is changed by setting of
aul
=
1
or
2
.
Refer to page L-1 about each rated output current.
Note 2: Parameter
aul
is displayed as “0” during reading after this is set.
Note 3: Present setting of inverter overload characteristic can be confirmed by status monitor.
Refer to monitor “Overload and region setting” of section 8.2.1.
6) Overload alarm level
f657
When the motor overload level reaches to
f657
setting value (%) of overload trip (
ol2
) level, “
l
” will be
displayed on the left side digit and the “
l
” and output frequency monitor will be blinking alternately on
overload alarm status.
Overload alarm signal can be output from output terminal.
[Parameters settings]
Title
Function
Adjustment range
Default setting
f657
Overload alarm level
10-100 (%)
50
[Example of setting]: Assigning the overload alarm to the OUT terminal.
Title Function
Adjustment
range Setting
f131
Output terminal selection 2A (OUT)
0-255
16: POL
17 is reverse signal.
time
[s]
f631
=
0
60
0
105%
120%
Monitored output current [%]
100%: Inverter rated output current
Содержание Q9 Plus ASD
Страница 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Страница 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Страница 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Страница 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Страница 429: ......
Страница 430: ......