E6581611
F-143
6
6.38.4 Open network option
c700
to
c830
: CANopen communication parameters
c000
to
c119
,
c900
to
c909
: Communication option common
parameters
c120
to
c149
: CC-Link option parameters
c150
to
c199
: ProfiBus DP option parameters
c200
to
c249
: DeviceNet option parameters
c400
to
c449
,
c850
to
c899
: EtherCAT option parameters
c500
to
c549
: EtherNet common parameters
c550
to
c599
: EtherNet/IP option parameters
c600
to
c649
: Modbus TCP option parameters
+
CANopen option (Type: CAN001Z, CAN002Z, CAN003Z)
CC- Link option
(Type: CCL003Z)
ProfiBus DP option
(Type: PDP003Z)
DeviceNet option
(Type: DEV003Z)
EtherNet / IP-Modbus TCP option (Type: IPE002Z)
EtherCAT option
(Type: IPE003Z)
⇒
Refer to each Instruction Manual of option for details.
6.39 Permanent
magnet
motors
f910
: Step-out detection current level
f911
: Step-out detection time
f912
: q-axis inductance
f913
: d-axis inductance
f915
: Factory specific coefficient 9L
•
Function
If the permanent magnet motor (PM motor) steps out and if the exciting current increases (it increases
in such a case) and remains above the value set with
f910
for the period of time set with
f911
,
the inverter will judge the motor to be stepping out and trip it. At that time, the trip message
"
sout
" is displayed.
Содержание Q9 Plus ASD
Страница 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Страница 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Страница 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Страница 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Страница 429: ......
Страница 430: ......