Q7 ASD Installation and Operation Manual
OUT6 On Delay
Program
⇒
Terminal Delays
⇒
OUT6 On Delay
This parameter delays the response of the OUT6 output contacts by the
programmed value (see waveforms at
).
The delay may be increased to prevent relay chatter.
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT6 Terminal
Program
⇒
Output Terminals
⇒
OUT6 Terminal
This parameter sets the functionality of the OUT6 output contacts to 1 of the 58
possible functions that are listed in
The on and off delay times of the OUT6 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output contacts must be specified as Normally Open or
Normally Closed.
Parameter Type — Selection List
Factory Default — Reach Speed
Changeable During Run — No
OUT7 Off Delay
Program
⇒
Terminal Delays
⇒
OUT7 Off Delay
Once the condition is met to change the state of the OUT7 output contacts, this
parameter delays the response of the contacts by the programmed value (see
waveforms at
The on and off delay times of the OUT7 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT7 On Delay
Program
⇒
Terminal Delays
⇒
OUT7 On Delay
This parameter delays the response of the OUT7 output contacts by the
programmed value (see waveforms at
).
The delay may be increased to prevent relay chatter.
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT7 Terminal
Program
⇒
Output Terminals
⇒
OUT7 Terminal
This parameter sets the functionality of the OUT7 output contacts to 1 of the 58
possible functions that are listed in
The on and off delay times of the OUT7 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output contacts must be specified as Normally Open or
Normally Closed.
Parameter Type — Selection List
Factory Default — OC Alarm
Changeable During Run — No