Q7 ASD Installation and Operation Manual
107
RX Torque Reference #1
Program
⇒
Freq Settings
⇒
RX Torque Ref #1
This parameter is used to set the direction, gain, and bias of the RX input
terminal when the RX terminal is used as the control input while operating in
the Torque Control mode.
RX Input Torque Control Setup
Perform the following setup to allow the system to receive Torque control input
at the RX input terminal:
• Program
⇒
Utility Group
⇒
Frequency Mode
⇒
Rx.
• Program
⇒
Utility Group
⇒
Command Mode
⇒
Terminal Block.
• Provide a Run command (F and/or R).
Torque Control
Perform the following setup to allow the system to perform Torque control
from the RX input terminal:
• Set
,
• Set the RX input signal level (RX Speed Ref #1) that represents the
• Set
, and
• Set the RX input signal level (RX Speed Ref #2) that represents the
This is accomplished by establishing an associated V/f output pattern for a
given RX input level.
This parameter sets RX Torque Reference #1 and is the output torque value
that is associated with the setting of RX Speed Reference #1 when operating in
the Torque control mode.
This value is entered as -250 to +250% of the rated torque.
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — -250.0
Maximum — +250.0
Units — %
Torque Settings
RX Torque Reference #2
Program
⇒
Freq Settings
⇒
RX Torque Ref #2
This parameter is used to set the direction, gain, and bias of the RX input
terminal when the RX terminal is used as the control input while operating in
the Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a
given RX input level.
for further information on this setting.
and is the output torque value
that is associated with setting of
Torque control mode.
This value is entered as -250 to +250% of the rated torque.
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — -250.0
Maximum — +250.0
Units — %