54
Q7 ASD Installation and Operation Manual
Brake Fault Time
Program
⇒
Protection
⇒
Brk Fault Time
After a brake failure has occurred, the user-set Brake Fault Time clock setting
will begin to count down. Once this time has elapsed, a signal will be provided
to indicate that the brake has failed.
This signal may be used to halt a related system or to notify the user.
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 10.00
Units — Seconds
Command Mode
Program
⇒
Utility Group
⇒
Command Mode
The Command Mode Selection establishes the source of the command input
for the ASD. Command inputs include Run, Stop, Forward, etc.
Settings:
(Use) Control Terminal Strip) Terminal Block
(Use) LED Keypad
(Use) Common Serial (TTL)
(Use) RS232/485
(Use) Communication Card
Parameter Type — Selection List
Factory Default — Terminal Block
Changeable During Run — No
Communications Data Type
Program
⇒
Comm Settings
⇒
Comm Data Type
In the event of a communication error during a transmission, the command that
was transmitted may be cleared or held.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Settings:
0 — Command Request Cleared
1 — Command Request Held
Parameter Type — Selection List
Factory Default — 0
Changeable During Run — No
Commercial Power Switching Freq. Hold Time
Program
⇒
Special Controls
⇒
Comm Hold Time
This parameter determines the amount of time that the connection to
commercial power is maintained once the switch-to-drive-output criteria has
been met.
Parameter Type — Selection List
Factory Default — 2.00
Changeable During Run — No
Minimum — 0.10
Maximum — 10.00
Units — Seconds