Q7 ASD Installation and Operation Manual
R Terminal Delay
Program
⇒
Terminal Delays
⇒
R Delay
This parameter delays the response of the ASD to any change in the R terminal
input by the programmed value.
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
RR Speed Frequency #1
Program
⇒
Freq Settings
⇒
RR Speed Freq #1
This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Speed
Control mode.
RR Input Speed Control Setup
Perform the following setup to allow the system to receive Speed control input
at the RR input terminal:
• Program
⇒
Utility Group
⇒
Frequency Mode
⇒
RR.
• Program
⇒
Utility Group
⇒
Command Mode
⇒
Terminal Block.
• Provide a Run command (F and/or R).
Speed Control
Perform the following setup to allow the system to perform Speed control from
the RR input terminal:
• Set RR Speed Frequency #1,
• Set the RR input signal level (RR Speed Ref #1) that represents RR Speed
Frequency #1,
• Set RR Speed Frequency #2, and
• Set the RR input signal level (RR Speed Ref #2) that represents RR Speed
Frequency #2.
Once set, as the RR input voltage changes the output frequency of the ASD will
vary in accordance with the above settings.
This parameter sets RR Speed Frequency #1 and is the frequency that is
associated with the setting of RR Speed Reference #1 when operating in the
Speed Control mode.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 80.0
Units — Hz
Frequency Settings
RR Speed Frequency #2
Program
⇒
Freq Settings
⇒
RR Speed Freq #2
This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Speed
Control mode.
See RR Speed Frequency #1 for further information on this setting.
This parameter sets RR Speed Frequency #2 and is the frequency that is
associated with the setting of RR Speed Reference #2 when operating in the
Speed Control mode.
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 80.0
Units — Hz