66
Q7 ASD Installation and Operation Manual
FM Terminal Assignment
Program
⇒
Meter Terminal Adjustment Parameters
⇒
FM
This setting determines the output function of the FM analog output terminal.
The FM output terminal produces an output current that is proportional to the
magnitude of the function assigned to this terminal. The available assignments
for this output terminal are listed in
The FM analog output has a maximum resolution of 1/1024. SW-2 may be
switched to allow for the full-range output to be either 0 – 1 mA or 4 – 20 mA
when providing an output current, or either 0 – 1 or 1 – 7.5 volts when
providing an output voltage at this terminal.
Parameter Type — Selection List
Factory Default — Output Frequency
Changeable During Run — Yes
FP Terminal Adjustment
Program
⇒
Output Terminals
⇒
FP Terminal Adj
This parameter sets the full-scale reading of the FP terminal. The full-scale
reading of the monitored variable selected in FP Terminal Setting may be set
here.
Parameter Type — Numerical
Factory Default — 3.840
Changeable During Run — Yes
Minimum — 1.000
Maximum — 43.200
Units — kHz
FP Terminal Setting
Program
⇒
Output Terminals
⇒
FP Terminal Set
This parameter commands the multifunction programmable FP terminal to
monitor the value of 1 of 31 possible system functions. As the monitored
function changes in magnitude or frequency, the pulse count of the FP output
pulse train changes in direct proportion to changes in the monitored function.
As the monitored value goes up so does the pulse count of the FP output.
Note: The duty cycle of the output pulse train remains at
65 ±5.0 µ S.
Possible assignments for this output terminal are listed in
.
Parameter Type — Selection List
Factory Default — Output Frequency
Changeable During Run — Yes
Frequency Command Panel
Program
⇒
PID Setup
⇒
Freq Cmd Pnl
While operating using PID control, this parameter sets the reference frequency.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq.
Units — Hz