78
Q7 ASD Installation and Operation Manual
MS Relay (status ANDED) with ST
Program
⇒
Protection
⇒
MS Relay with ST
The MS1 AUX relay circuit is normally open and is in series with the ST-to-
CC connection.
After normal system power is available the MS1 AUX relay circuit closes and
completes the ST-to-CC connection.
Settings:
Disabled
Enabled
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Multiplying Input Selection
Program
⇒
Protection
⇒
Mult Input Sel
This parameter Enables/Disables the feature that allows for the external
adjustment of the Output Frequency.
Selecting either of the input methods listed enables this feature. The selected
input is used as a multiplier of the programmed Output Frequency.
If operating using the LED Keypad Option and Setting is selected, the value
entered at LED Option Override Multiplication Gain is used as the
multiplier.
Settings:
Disabled
VI/II
RR
RX
RX2 (option)
Setting (LED Keypad Option Only)
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Number of Retries
Program
⇒
Protection
⇒
Number Retries
After a trip has occurred, this parameter sets the number of times that an
automatic system restart is attempted for a qualified trip.
The trip conditions listed below will not initiate the Retry function:
•
OCA1, 2, or 3 (Arm Short Ckt),
•
EPH1 (Input Phase Failure),
•
EPH0 (Output Phase Failure),
•
OCL (Startup Overcurrent),
•
EF1 or 2 (Ground Fault),
•
EMG (Emergency Off),
•
EEP1 (EEPROM Fault),
•
Err2 through Err9 (Main RAM/ROM Fault),
•
E-10 (Sink/Source Error),
•
13 (Speed Error), or
•
17 (Key Error).
General Safety Information on pg. 1
for further
information on this setting.
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 00
Maximum — 10