Q7 ASD Installation and Operation Manual
121
Switch-on-the-Fly
Program
⇒
Special Controls
⇒
Switch-on-the-Fly
The ability to switch between the Manual and Auto modes while running.
Settings:
Disabled
Enabled
Maintain Motion
Seamless
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Torque Boost #1
Program
⇒
Motor Settings
⇒
Torque Boost #1
The Motor #1 Torque Boost function is used to increase the low frequency
torque for high-inertia loads by increasing the output voltage at frequencies
below ½ of the #1 Base Frequency setting.
The value programmed as a boost percentage establishes an output voltage vs.
output frequency relationship to be used to start the motor or to provide
smoother operation.
Note: Setting an excessive Torque Boost level may cause nuisance
tripping and mechanical stress to loads.
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.0
Units — %
Torque Boost #2
Program
⇒
Motor Settings
⇒
Torque Boost #2
The Motor #2 Torque Boost function is used to increase the low frequency
torque for high inertia loads by increasing the output voltage at frequencies
below ½ of the #2 Base Frequency setting).
This parameter is used only when the parameters for motor set #2 are
configured and selected. Motor set #2 may be selected by a properly configured
input terminal.
See parameter Motor #1 Torque Boost for more information on this setting.
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.0
Units — %
Torque Boost #3
Program
⇒
Motor Settings
⇒
Torque Boost #3
The Motor #3 Torque Boost function is used to increase the low frequency
torque for high inertia loads by increasing the output voltage at frequencies
below ½ of the #3 Base Frequency setting.
This parameter is used only when the parameters for motor set #3 are
configured and selected. Motor set #3 may be selected by a properly configured
input terminal.
See parameter Motor #1 Torque Boost for more information on this setting.
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.0
Units — %