RS485 Baud Rate
Program
⇒
Comm Settings
⇒
RS485 Baud Rate
This parameter sets the RS485 baud rate.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Settings:
1200
2400
4800
9600
19200
38400
Parameter Type — Selection List
Factory Default — 9600
Changeable During Run — Yes
RS485 Comm Time-Out Action
Program
⇒
Comm Settings
⇒
485 Timeout Act
This parameter plays a role in the setup of the communications network by
determining the action to be taken in the event of a time-out (Time-Out
Action).
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Settings:
None
485-Alarm – TTL-None
485-Trip – TTL-None
485-None – TTL-Alarm
485-Alarm – TTL-Alarm
485-Trip – TTL-Alarm
485-None – TTL-Trip
485-Alarm – TTL-Trip
485-Trip – TTL-Trip
Parameter Type — Selection List
Factory Default — 485-Alarm – TTL-
None
Changeable During Run — Yes
RS485 Comm Time-Out Time
Program
⇒
Comm Settings
⇒
485 Timeout Time
This parameter plays a role in the setup of the communications network by
setting the time that no activity may exist over the communications link before
the link is severed (Time Out).
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 100