Q7 ASD Installation and Operation Manual
127
VI/II Speed Reference #1
Program
⇒
Freq Settings
⇒
VI/II Spd Ref #1
This parameter is used to set the gain and bias of the VI/II input terminal when
the VI/II terminal is used as the control input while operating in the Speed
Control or the Torque Control mode.
for further information on this setting when
used for Speed control.
for further information on this setting when
used for Torque control.
This parameter sets the VI/II input level that is associated with
when operating in the Speed control mode or is associated with
when operating in the Torque control mode.
This value is entered as 0.0% to 100% of the 0.0 to +10 VDC VI/II input signal
range.
The default value for this parameter is 20%. The II input is commonly used for
the 4 – 20 mA current loop signal where 4 mA equals 20% of a 20 mA signal.
If the VI input is used (0 – 10 VDC input), this parameter may be changed to
0.0% (of the input signal).
Parameter Type — Numerical
Factory Default — 20.00
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %
VI/II Speed Reference #2
Program
⇒
Freq Settings
⇒
VI/II Spd Ref #2
This parameter is used to set the gain and bias of the VI/II input terminal when
the VI/II terminal is used as the control input while operating in the Speed
Control or the Torque Control mode.
for further information on this setting when
used for Speed control.
for further information on this setting when
used for Torque control.
This parameter sets the VI/II input level that is associated with
when operating in the Speed control mode or is associated with
when operating in the Torque control mode.
This value is entered as 0.0% to 100% of the 0.0 to +10 VDC VI/II input signal
range.
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %