76
Q7 ASD Installation and Operation Manual
Motor 150% Run Time
Program
⇒
Protection
⇒
Motor 150% Time
This parameter establishes a time that the motor may operate at 150% of its
rated current before tripping. This setting applies the time/150% reference to
the individual settings of each motor (e.g., this setting references 150% of the
Thermal Protection
setting for the #1 motor).
The unit will trip sooner than the time entered here if the overload is greater
than 150%.
Parameter Type — Numerical
Factory Default — 600
Changeable During Run — Yes
Minimum — 10
Maximum — 2400
Units — Seconds
Motor Capacity
Program
⇒
Motor Settings
⇒
Motor Capacity
This user-input parameter identifies the wattage rating of the motor.
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — No
Minimum — 0.10
Maximum — (ASD-dependent)
Units — kW
Motor Constant 1
Program
⇒
Motor Settings
⇒
Motor Constant 1
This parameter is the measurement of the stator resistance and is considered a
Motor Constant (unchanging). This value is used in conjunction with other
constants to tune the motor.
To use Vector Control, Automatic Torque Boost, or Automatic Energy-
saving, the Motor Constant setting (motor tuning) is required.
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — No
Minimum — 0.0
Maximum — 100,000 M
Ω
Units —
Ω
Motor Constant 2
Program
⇒
Motor Settings
⇒
Motor Constant 2
This parameter is the measurement of the rotor resistance and is considered a
Motor Constant (unchanging). This value is used in conjunction with other
constants to tune the motor.
This setting (motor tuning) is required to use the Vector Control, Automatic
Torque Boost, or Automatic Energy-saving functions.
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — No
Minimum — 0.00
Maximum — Open
Units —
Ω
Motor Constant 3
Program
⇒
Motor Settings
⇒
Motor Constant 3
This parameter is used to input the excitation inductance for the motor. This
value is used in conjunction with other constants to tune the motor.
This setting (motor tuning) is required to use the Vector Control, Automatic
Torque Boost, or Automatic Energy-saving functions.
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — No
Minimum — 0.00
Maximum — 6500.0
Units — µH