Q7 ASD Installation and Operation Manual
73
LOD Boost Level
Program
⇒
PID Setup
⇒
LOD Boost Level
The Low Output Disable feature adds the user-input frequency value to the
commanded frequency (Hz).
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq.
Units — Hz
LOD Boost Time
Program
⇒
PID Setup
⇒
LOD Boost Time
The Low Output Disable Boost Time sets the on-time timer for the LOD
Boost function.
Once expired, the LOD Boost function ceases.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
LOD Delay Time
Program
⇒
PID Setup
⇒
LOD Delay Time
The Low Output Disable Delay Time sets the amount of time that the LOD
Start Level criteria must be met and maintained for the LOD function to be
initiated.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
LOD Feedback Level
Program
⇒
PID Setup
⇒
LOD Feedback Lvl
The Low Output Disable Feedback Level sets a frequency level that, until the
output of the ASD drops below this setting, the Restart Delay Timer does not
start.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq.
Units — Hz
LOD Input Selection
Program
⇒
PID Setup
⇒
LOD Input Sel
Enables/Disables the LOD function and, if enabled, selects a stopping method.
Settings:
Disabled
Enabled — Decel Stop
Enabled — Coast Stop
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes