
50
Q7 ASD Installation and Operation Manual
Autotune Enable
Program
⇒
Motor Settings
⇒
Autotune Enable
This parameter Enables/Disables the Autotune function.
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — No
Base Frequency 1
Program
⇒
Motor Settings
⇒
Base Frequency #1
The Base Frequency setting determines the frequency at which the output
voltage of the ASD reaches its maximum setting. The maximum voltage setting
cannot be more that the input voltage (see the
parameter). There are four Base Frequency profile settings: #1 – #4.
Note: For proper motor operation, the Base Frequency is
normally set for the name-plated frequency of the motor.
Parameter Type — Numerical
Factory Default — 60.0
Changeable During Run — Yes
Minimum — 25.0
Maximum — 299.0
Units — Hz
Base Frequency 2
Program
⇒
Motor Settings
⇒
Base Frequency 2
The Motor #2 Base Frequency setting determines the frequency at which the
output voltage of the ASD reaches its maximum setting. The maximum voltage
setting cannot be more that the input voltage (see the
parameter). There are four Base Frequency profile settings: #1 – #4.
This parameter is used only when the parameters for motor set #2 are
configured and selected. Motor set #2 may be activated via a properly
configured discrete input terminal.
For proper motor operation, the Base Frequency should be set for the name-
plated frequency of the motor.
Parameter Type — Numerical
Factory Default — 60.0
Changeable During Run — Yes
Minimum — 25.0
Maximum — 299.0
Units — Hz
Base Frequency 3
Program
⇒
Motor Settings
⇒
Base Frequency 3
The Motor #3 Base Frequency setting determines the frequency at which the
output voltage of the ASD reaches its maximum setting. The maximum voltage
setting cannot be more that the input voltage (see the
parameter). There are four Base Frequency profile settings: #1 – #4.
This parameter is used only when the parameters for motor set #3 are
configured and selected. Motor set #3 may be activated via a properly
configured discrete input terminal.
For proper motor operation, the Base Frequency should be set for the name-
plated frequency of the motor.
Parameter Type — Numerical
Factory Default — 60.0
Changeable During Run — Yes
Minimum — 25.0
Maximum — 299.0
Units — Hz