Q7 ASD Installation and Operation Manual
159
Cable/Terminal Specifications
Note:
The following ratings are guidelines and shall not be the sole determining factor of the
lug or wire size used with the Q7 ASD. Application-specific applicables, wire insulation
type, conductor material, and local and regional regulations are but a few of the
considerations when selecting the actual lug and wire type to be used with the Q7 ASD.
Note:
Use only 75° C copper wire/cable for motor and power connections.
Table 19. Q7 ASD 230 Volt Drive Cable/Terminal Specifications.
Model No.
VT130Q7U
Circuit
Breaker
Rating
(Amps)
Typical Wire/Cable Size (AWG or kcmil)
Lug Size
Input/Output
Power
AM, FM, and II
Terminals
Control Terminal
Strip
ASD Input/Output Power
Lug Wire Capacity
(AWG or kcmil)
2010B
15
14
20
(3-core shield)
18
(2-core shield)
24 – 8
2015B
15
14
2025B
15
14
2035B
20
14
2055B
30
10
2080B
50
8
2110B
75
8
18 – 4
2160B
75
6
2220B
100
4
2270B
125
3
16 – 3
2330B
150
2
10 – 1/0
2400B
200
2/0
12 – 4/0
2500B
250
3/0
2600B
300
250 – *1/0
*6 – 250
2750B
400
*3/0
210KB
500
*250
*1/0 – 500
212KB
600
*350
215KB
700
*400
Note:
(*) Indicates that the item is one of a set of two parallel cables.