Q7 ASD Installation and Operation Manual
99
RES Terminal
Program
⇒
Input Terminals
⇒
RES Terminal
This parameter selects the functionality of the RES discrete input terminal.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable RES terminal to 1 of the 69 possible
functions that are listed in
.
Parameter Type — Selection List
Factory Default — Reset
Changeable During Run — No
RES Terminal Delay
Program
⇒
Terminal Delays
⇒
RES Delay
This parameter delays the response of the ASD to any change in the RES
terminal input by the programmed value (see waveforms at
).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Ridethrough Mode
Program
⇒
Protection
⇒
Ridethrough Mode
Enables/Disables the Ridethrough function.
In the event of a momentary power outage, when enabled, the Ridethrough
function uses regenerative energy to maintain the control circuitry settings.
Regenerated energy is not used to drive the motor.
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Ridethrough Time
Program
⇒
Protection
⇒
Ridethrough
This parameter determines the length of the Ridethrough time. The
Ridethrough will be maintained for the number of seconds set using this
parameter.
Note: The actual Ridethrough Time is load-dependent.
Parameter Type — Numerical
Factory Default — 2.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 320.0
Units — Seconds
R Terminal
Program
⇒
Input Terminals
⇒
R Terminal
This parameter selects the functionality of the R discrete input terminal.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable R terminal to 1 of the 69 possible
functions that are listed in
.
Parameter Type — Selection List
Factory Default — Reverse
Changeable During Run — No