Q7 ASD Installation and Operation Manual
Shaft Stationary Control
Program
⇒
Protection
⇒
Shaft Stationary
This parameter Enables/Disables a continuous DC injection at half of the
amperage setting of the DC Injection Braking Current parameter into a
stopped motor. This feature is useful in preheating the motor or to keep a
stopped motor from spinning freely.
Motor Shaft Stationary Control starts after the DC injection brake stops the
motor and continues until ST-to-CC is opened, power is turned off, receiving an
Emergency Off command, or this parameter is changed.
To use this feature, a non-zero entry at the DC Injection Braking Start
Frequency parameter is required.
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Short Circuit Test
Program
⇒
Protection
⇒
Short CKT Test
This parameter determines when the system will perform an Output Short
Circuit test.
Settings:
First Time (each startup from off or reset)
Standard (each startup)
Parameter Type — Selection List
Factory Default — Standard
Changeable During Run — No
Short Circuit Time
Program
⇒
Protection
⇒
Short CKT Time
This parameter sets the pulse width of the ASD output pulse that is applied to
the motor during an Output Short Circuit test.
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — No
Minimum — 1
Maximum — 100
Units — µS