70
Q7 ASD Installation and Operation Manual
Jump 1 Bandwidth
Program
⇒
Special Controls
⇒
Jump 1 Bandwidth
In conjunction with the Jump Frequency #1 setting, this parameter establishes
a user-defined plus-or-minus frequency range for the Jump Frequency 1
setting.
During acceleration, the output frequency of the ASD will hold at the frequency
of the lower level of the Jump Frequency (1, 2, or 3) range until the
programmed acceleration ramp reaches the upper level of the Jump Frequency
range. Then, the output frequency of the ASD will accelerate to the upper level
of the Jump Frequency range and continue upward as programmed.
During deceleration, the output frequency of the ASD will hold at the frequency
of the upper level of the Jump Frequency range until the programmed
deceleration ramp reaches the lower level of the Jump Frequency range. Then,
the output frequency of the ASD will decelerate to the lower level of the Jump
Frequency range and continue downward as programmed.
If overlapping Jump Frequency bandwidths are set up, the system will respond
with one bandwidth setting that includes the total range.
Once set up and enabled, it is on in all control modes.
User-selected frequencies may be jumped to avoid the negative effects of
mechanical resonance.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.00
Units — Hz
Jump 2 Bandwidth
Program
⇒
Special Controls
⇒
Jump 2 Bandwidth
This parameter establishes a plus-or-minus value for Jump Frequency 2.
See the
parameter for further information on this setting.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.0
Units — Hz
Jump 3 Bandwidth
Program
⇒
Special Controls
⇒
Jump 3 Bandwidth
This parameter establishes a plus-or-minus value for Jump Frequency 3.
See the
parameter for further information on this setting.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.0
Units — Hz
Jump Frequency 1
Program
⇒
Special Controls
⇒
Jump Frequency 1
This parameter establishes the Jump Frequency 1 setting.
Once set up and enabled, it is on in all control modes.
See the
parameter for further information on this setting.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq.
Units — Hz